PRODUCT DETAILS

Control Panel FS-7000CP

Power Source 24 V DC, M3 screw terminal, distance between barriers: 6.4 mm
Current Consumption 200 mA
Input EV: 0 dB*, 600 Ω, unbalanced, removable terminal block (2 pins)
Timer: 0 dB*, 600 Ω, unbalanced, removable terminal block (4 pins)
Paging: -60/-20 dB*, 600 Ω, balanced, removable terminal block (5 pins)
RF (Remote microphone): 0 dB*, 600 Ω, balanced,
removable terminal block (3 pins)
Preinstalled microphone (accessory): -55 dB*, 600 Ω, unbalanced,
circular connector (4 pins)
AUX: -20 dB*, 600 Ω, unbalanced, removable terminal block (2 pins)
BGM 1: -60/0 dB*, 600 Ω, balanced, removable terminal block (3 pins)
BGM 2 - 4: -20 dB*, 10 kΩ, unbalanced, RCA jack
Output Priority output: 0 dB*, 600 Ω, balanced, removable terminal block (3 pins)
(Outputs signals other than BGM 1 - 4 input signals when output
is set to 2-channel broadcast mode.)
BGM output: 0 dB*, 600 Ω, balanced, removable terminal block (3 pins)
(Outputs BGM 1 - 4 signals.)
Frequency Response 50 - 15,000 Hz, within ±3 dB (1 kHz)
Tone Control ±10 dB at 100 Hz and 10 kHz
S/N Ratio Over 60 dB
Distortion Under 1%
Priority Function Priority output: Preinstalled microphone > EV (emergency broadcast mode)
Timer > Paging > Remote microphone >
Preinstalled microphone, AUX > BGM 1
BGM 2 - 4 (general-purpose broadcast mode)
BGM output: BGM 1 BGM 2 - 4 (by muting function setting)
Electronic Tone Ascending 4-tone chime
External Control Input Timer: No-voltage make contact input, open voltage: 26 V DC,
short-circuit current: Under 2 mA, removable terminal block (4 pins)
Paging: No-voltage make contact input, open voltage: 26 V DC,
short-circuit current: Under 2 mA, removable terminal block (5 pins)
Automatic fire alarm system (10 zones):
No-voltage make contact input, open voltage: 26 V DC,
short-circuit current: Under 5 mA, removable terminal block (12 pins)
Output Control 10 individual zones + all-zone call or 10 group zones + all-zone call (when
optional FS-7000GM is connected)
(individual zones expandable to up to 200 zones using FS-7010CP)
Operating Section Zone selection key, All-zone call button (general-purpose/general urgency all-
zone call selectable), Broadcast reset button and Chime button
Display Section Power indicator, All-zone call indicator, Zone indicators, Busy indicator (timer,
paging, remote microphone and main system), Speaker line short-circuit indicator
Operating Temperature 0℃ to +40℃
Operating Humidity Under 90% RH (no condensation)
Finish Panel: Aluminum, black, alumite
Dimensions 482 (W) × 132.6 (H) × 376.9 (D) mm
Weight 5.2 kg
Accessory Microphone …1, Removable terminal plug (2 pins) …2,
Removable terminal plug (3 pins) …4, Removable terminal plug (4 pins) …1,
Removable terminal plug (5 pins) …1, Removable terminal plug (12 pins) …1

 